Question: A balanced three-phase transformer bank with the Î -Y connection depicted in Fig. 13.137 is used to step down line voltages from 4,500 V rms
A balanced three-phase transformer bank with the Î -Y connection depicted in Fig. 13.137 is used to step down line voltages from 4,500 V rms to 900 V rms. If the transformer feeds a 120-kVA load, find:
(a) The turns ratio for the transformer,
(b) The line currents at the primary and secondary sides.
.png)
500 V 900 V 42 kVA Three-phase load
Step by Step Solution
3.42 Rating (158 Votes )
There are 3 Steps involved in it
a n V Ls 3 V Lp 9004500 3 ... View full answer