Question: A plant consumes 75 kW at a power factor of 0.70 lagging from a 240-V rms 60 Hz line. Determine the value of the capacitor
A plant consumes 75 kW at a power factor of 0.70 lagging from a 240-V rms 60 Hz line. Determine the value of the capacitor that when placed in parallel with the load will change the load power factor to 0.9 lagging.
Step by Step Solution
3.48 Rating (164 Votes )
There are 3 Steps involved in it
Since the original power factor is 07 lagging the power factor angle is GOLD cos 07 4557 Then Hen... View full answer