A three-phase, 6600-V main bus feeds a three-phase, 2-MVA, 6600/480-V transformer with 5% impedance. The transformer powers
Question:
A three-phase, 6600-V main bus feeds a three-phase, 2-MVA, 6600/480-V transformer with 5% impedance. The transformer powers multiple loads, including a three-phase, 500-hp motor as shown in the following figure. Determine the symmetrical rms fault current through CB1, CB2, CB3, and CB4 under a three-phase fault at the spark location assuming:
(1) All cable impedances are negligible,
(2) The bus has multiple generators of large capacity (i.e., infinite bus), and
(3) The motor delivering rated load before the fault with 92% efficiency and 90% pf lagging.