Question: Consider the schematic diagram of a controlled blending process shown in Fig. 8.1. The control objective is to control the mass fraction of the exit
Consider the schematic diagram of a controlled blending process shown in Fig. 8.1. The control objective is to control the mass fraction of the exit stream, x, by adjusting inlet flow rate, w2, using a feedback controller. The mass fractions of a key chemical component in the inlet streams, x1and x2, are constant, and mass flow rate w1is a disturbance variable. The liquid volume V is constant. The composition sensor / transmitter (AT) and the current to pressure transducer (I/P) are both direct acting devices. What is the minimum amount of information you would need in order to decide whether the feedback controller, AC, should be reverse acting or direct acting?

I/P < Electrical signal Pneumatic signal AC
Step by Step Solution
3.44 Rating (157 Votes )
There are 3 Steps involved in it
Two pieces of information are needed to specify controller action i Is the control va... View full answer