Question

1 Approved Answer

A three-phase Y-connected synchronous generator is rated 120 MVA, 13.8 kV, 0.8-PF lagging, and 60 Hz. Its synchronous reactance is 1.2 per phase, and

A three-phase Y-connected synchronous generator is rated 120 MVA, 13.8 kV, 0.8-PF lagging, and 60 Hz. Its synchronous reactance is 1.2 Ω per phase, and its armature resistance is 0.1Ω per phase.

(a) What is its voltage regulation?

(b) What would the voltage and apparent power rating of this generator be if it were operated at 50 Hz with the same armature and field losses as it had at 60 Hz?

(c) What would the voltage regulation of the generator be at 50 Hz?

Step by Step Solution

3.44 Rating (154 Votes )

There are 3 Steps involved in it

Step: 1

It is given that The rating of generator is S rated 120 MVA The terminal voltage of the generator is V T 138 kV The power factor of the generator is C... blur-text-image

Get Instant Access to Expert-Tailored Solutions

See step-by-step solutions with expert insights and AI powered tools for academic success

Step: 2

blur-text-image

Step: 3

blur-text-image

Document Format ( 2 attachments)

PDF file Icon
6093adf0687a0_24055.pdf

180 KBs PDF File

Word file Icon
6093adf0687a0_24055.docx

120 KBs Word File

Ace Your Homework with AI

Get the answers you need in no time with our AI-driven, step-by-step assistance

Get Started

Recommended Textbook for

College Physics

Authors: Jerry D. Wilson, Anthony J. Buffa, Bo Lou

7th edition

9780321571113, 321601831, 978-0321601834

More Books

Students also viewed these Physics questions

Question

1. Describe the Good Lives Model of offender rehabilitation

Answered: 1 week ago