=+8-45. A room has an internal heat gain of 2000 W. 50 percent radiative and 50 percent

Question:

=+8-45.

A room has an internal heat gain of 2000 W. 50 percent radiative and 50 percent convective.

from 8:00 A.M. to 6:00 P.M ., and 200 W with the same radiative-convective split the rest of the day. If the room matches the MW I zone from Table 8-21, determine the hourly cooling loads.

Plot and compare the hourly heat gains vs. the hourly cooling loads.

Step by Step Answer: