Choosing system bases to be $240 / 24 mathrm{kV}$ and $100 mathrm{MVA}$, redraw the per-unit equivalent circuit
Question:
Choosing system bases to be $240 / 24 \mathrm{kV}$ and $100 \mathrm{MVA}$, redraw the per-unit equivalent circuit for Problem 3.39.
Data From Problem 3.39:-
The leakage reactance of a three-phase, \(300-\mathrm{MVA}, 230 \mathrm{Y} / 23 \Delta-\mathrm{kV}\) transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume American standard phase shift.