The open-circuit terminal voltage of a three-phase, 60-Hz synchronous generator is found to be 15.4 kV rms
Question:
The open-circuit terminal voltage of a three-phase, 60-Hz synchronous generator is found to be 15.4 kV rms line-to-line when the field current is 420 A.
a. Calculate the stator-to-rotor mutual inductance Laf.
b. Calculate the open-circuit terminal voltage if the field current is held constant while the generator speed is reduced so that the frequency of the generated voltage is 50 Hz.
Fantastic news! We've Found the answer you've been seeking!
Step by Step Answer:
Related Book For
Question Posted: