Question: A 50-Hz, two-pole, 750 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.75 and achieves rated open-circuit terminal voltage at a
A 50-Hz, two-pole, 750 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.75 Ω and achieves rated open-circuit terminal voltage at a field current of 120 A.
a. Calculate the armature-to-field mutual inductance.
b. The machine is to be operated as a motor supplying a 600 kW load at its rated terminal voltage. Calculate the internal voltage Eaf and the corresponding field current if the motor is operating at unity power factor.
c. For a constant load power of 600 kW, write a MATLAB script to plot the terminal current as a function of field current. For your plot, let the field current vary between a minimum value corresponding to a machine loading of 750 kVA at leading power factor and a maximum value corresponding to a machine loading of 750 kVA at lagging power factor. What value of field current produces the minimum terminal current? Why?
Step by Step Solution
3.42 Rating (152 Votes )
There are 3 Steps involved in it
part a part b Laf 2 V11rms 3wIf 600 x 10 3 2300 If 498 mH af V jXsa ... View full answer