Question: Saturated vapor R-134a leaves the evaporator in a heat pump system at 10C, with a steady mass flow rate of 0.1 kg/s. What is the
Saturated vapor R-134a leaves the evaporator in a heat pump system at 10°C, with a steady mass flow rate of 0.1 kg/s. What is the smallest diameter tubing that can be used at this location if the velocity of the refrigerant is not to exceed 7 m/s?
Step by Step Solution
3.29 Rating (152 Votes )
There are 3 Steps involved in it
Mass flow rate Eq63 m Vv AVv Exit state Tabl... View full answer