Question: Saturated vapor R-134a leaves the evaporator in a heat pump system at 10C, with a steady mass flow rate of 0.1 kg/s. What is the
Saturated vapor R-134a leaves the evaporator in a heat pump system at 10°C, with a steady mass flow rate of 0.1 kg/s. What is the smallest diameter tubing that can be used at this location if the velocity of the refrigerant is not to exceed 7 m/s?A hot air home heating system takes 0.25 m3/s air at 100 kPa, 17oC into a furnace and heats it to 52oC and delivers the flow to a square duct 0.2 m by 0.2 m at 110 kPa. What is the velocity in the duct?