A refrigeration process with interstage cooling uses refrigerant R134a. The outlet of the condenser is to be
Question:
A refrigeration process with interstage cooling uses refrigerant R134a. The outlet of the condenser is to be saturated liquid at 40°C. The evaporator is to operate at -20°C, and the outlet is saturated vapor. The economizer is to operate at 10°C. Refer to Fig. 5.10 for stream numbers in your solution.
(a) Determine the required flowrate of stream 1 if the cooling capacity of the unit is to be 8250 kJ/h.
(b) Determine the pressure of stream 3, and the work required by the first compressor if it has an efficiency of 85%.
(c) What are the flowrates of streams 7 and 6?
(d) What is the enthalpy of stream 4?
(e) Determine the work required by the second compressor (85% efficient) and the COP