In the figure below, a three-phase, 1000-kVA, 480-V, Y-connected generator with ungrounded neutral has armature resistance R
Question:
In the figure below, a three-phase, 1000-kVA, 480-V, Y-connected generator with ungrounded neutral has armature resistance Ra = 1% and subtransient reactance Xʺd = 10%. It feeds a three-phase, 75-kVA, 480/208-V transformer with R = 1% and X = 5%. The cable has R = 0.08 Ω and X = 0.026 Ω per phase per 1000 ft. For an L-L-L fault with no ground involved, 150 ft. away from the transformer terminals, determine the symmetrical rms value and the first offset peak of the fault current in a 150-ft. cable. Repeat the calculations to determine the circuit breaker fault current rating on the 75-kVA transformer secondary terminals.