Question

1 Approved Answer

A single-phase 120 kVA, 2400/240 V, 60-Hz distribution transformer is used as a step-down trans- former. The load, which is connected to the 240-V

A single-phase 120 kVA, 2400/240 V, 60-Hz distribution transformer is used as a step-down trans- former. The 

A single-phase 120 kVA, 2400/240 V, 60-Hz distribution transformer is used as a step-down trans- former. The load, which is connected to the 240-V secondary winding, absorbs 110 kVA at 0.85 power factor lagging and is at 230 V. Winding resistances are R-2 52 and R -0.05 52; leakage reactances are X = 2.5 2 and X-0.02 2. Calculate the following (using actual values): a) equivalent series impedance, referred to the primary b) primary voltage c) the real and reactive power supplied to the primary winding Using transformer ratings as base values, rework Problem in per-unit.

Step by Step Solution

3.37 Rating (156 Votes )

There are 3 Steps involved in it

Step: 1

Answer Given data Transformer rating 120 kVA Primary voltage VP 2400 V Secondary voltage VS 240 V Load power Sload 110 kVA Power factor cos 085 laggin... blur-text-image

Get Instant Access to Expert-Tailored Solutions

See step-by-step solutions with expert insights and AI powered tools for academic success

Step: 2

blur-text-image

Step: 3

blur-text-image

Ace Your Homework with AI

Get the answers you need in no time with our AI-driven, step-by-step assistance

Get Started

Recommended Textbook for

Fundamentals Of Electric Circuits

Authors: Matthew Sadiku, Charles Alexander

3rd Edition

978-0073301150, 0073301159

More Books

Students also viewed these Electrical Engineering questions

Question

=+9-7 Describe three alternative cost-plus pricing methods.

Answered: 1 week ago

Question

4. Greet students at the door to the class every day.

Answered: 1 week ago

Question

Find i0 in the circuit in Fig. 3.59. Figure 3.59 162 2i 4 A 0 2 4

Answered: 1 week ago