A lecture theatre having volume 1000m 3 is designed to seat 200 people. The air is conditioned
Question:
A lecture theatre having volume 1000m3 is designed to seat 200 people. The air is conditioned continuously by an inflow of fresh air at a constant rate V (in m3min–1). An average person generates 980cm3 of CO2 per minute, while fresh air contains 0.04% of CO2 by volume. Show that the percentage concentration x of CO2 by volume in the lecture theatre at time t (in min) after the audience enters satisfies the differential equation
If initially x(0) = 0.04, show that x(t) is an increasing function of t for t > 0. Deduce that the maximum x* of x (t) is given by
If the specification is that x does not exceed 0.06 (that is, 50% increase above fresh air), deduce that V must be chosen so that V > 980. Comment on this result.