Question:

(i) Consider the following data for an RBMK Reactor-Power \(1000 \mathrm{MW}(\mathrm{e}) / 3200 \mathrm{MW}\) th, coolant outlet temperature \(285^{\circ} \mathrm{C}\), Calculate coolant inlet temperature if the core flow rate is \(19,000 \mathrm{~kg} / \mathrm{s}\) and the specific heat of water is assumed to be \(6000 \mathrm{~J} / \mathrm{kg} /{ }^{\circ} \mathrm{C}\). 

(ii) Also calculate the core inlet temperature for AGR given in Table 3.2 rated at a thermal power of \(1620 \mathrm{MW}\) th if the core gas flow rate is \(4000 \mathrm{~kg} / \mathrm{s}\) and the specific heat of \(\mathrm{CO}_{2}\) is \(1220 \mathrm{~J} / \mathrm{kg} /{ }^{\circ} \mathrm{C}\).

Data From Table 3.2:-