A three-phase (34.5-mathrm{kV}) feeder supplying a 3.5-MVA load is protected by (80 mathrm{E}) power fuses in each

Question:

A three-phase \(34.5-\mathrm{kV}\) feeder supplying a 3.5-MVA load is protected by \(80 \mathrm{E}\) power fuses in each phase, in series with a recloser. The time-current characteristic of the 80E fuse is shown in Figure 10.43. Analysis yields maximum and minimum fault currents of 1000 and \(500 \mathrm{~A}\), respectively,

(a) To have the recloser clear the fault, find the maximum clearing time necessary for recloser operation.

(b) To have the fuses clear the fault, find the minimum recloser clearing time. Assume that the recloser operating time is independent of fault current magnitude.

image text in transcribed

Fantastic news! We've Found the answer you've been seeking!

Step by Step Answer:

Related Book For  book-img-for-question

Power System Analysis And Design

ISBN: 9781305632134

6th Edition

Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma

Question Posted: