Determine the equivalent (A B C D) parameters for the line in Problem 5.14 if it has
Question:
Determine the equivalent \(A B C D\) parameters for the line in Problem 5.14 if it has \(70 \%\) shunt reactive (inductors) compensation and \(40 \%\) series capacitive compensation. Half of this compensation is installed at each end of the line, as in Figure 5.14.
Problem 5.14
A \(500-\mathrm{km}, 500-\mathrm{kV}, 60-\mathrm{Hz}\), uncompensated three-phase line has a positivesequence series impedance \(z=0.03+j 0.35
\Omega / \mathrm{km}\) and a positivesequence shunt admittance \(y=j 4.4
\times 10^{-6} \mathrm{~S} / \mathrm{km}\). Calculate:
(a) \(Z_{c}\),
(b) \((\gamma l)\), and
(c) the exact \(A B C D\) parameters for this line.
Figure 5.14
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition
Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma