Each unit in Problem 12.5 is initially operating at one-half its own rating when the load suddenly

Question:

Each unit in Problem 12.5 is initially operating at one-half its own rating when the load suddenly increases by 100 MW. Determine

(a) the steadystate decrease in area frequency, and

(b) the MW increase in mechanical power output of each turbine. Assume that the reference power setting of each turbine-generator remains constant. Neglect losses and the dependence of load on frequency.

Problem 12.5

An area of an interconnected \(60-\mathrm{Hz}\) power system has three turbinegenerator units rated 200,300, and 500 MVA. The regulation constants of the units are \(0.03,0.04\), and 0.05 per unit, respectively, based on their ratings. Each unit is initially operating at one-half its own rating when the load suddenly decreases by \(150 \mathrm{MW}\). 