Equipment ratings for the five-bus power system shown in Figure 7.15 are given as follows: Generator G1:
Question:
Equipment ratings for the five-bus power system shown in Figure 7.15 are given as follows:
Generator G1: \(\quad 50 \mathrm{MVA}, 12 \mathrm{kV}, \mathrm{X}_{d}^{\prime \prime}=\mathrm{X}_{2}=0.20, \mathrm{X}_{0}=0.10\) per unit
Generator G2: \(\quad 100 \mathrm{MVA}, 15 \mathrm{kV}, \mathrm{X}_{d}^{\prime \prime}=0.2, \mathrm{X}_{2}=0.23, \mathrm{X}_{0}=0.1\) per unit
Transformer T1: \(50 \mathrm{MVA}, 10 \mathrm{kV}\) Y/138 kV Y, X \(=0.10\) per unit
Transformer T2: \(100 \mathrm{MVA}, 15 \mathrm{kV} \Delta / 138 \mathrm{kV} \mathrm{Y}, \mathrm{X}=0.10\) per unit
Each 138-kV line: \(X_{1}=40\) ohms, \(X_{0}=100\) ohms
Draw the zero-, positive-, and negative-sequence reactance diagrams using a \(100-\) MVA, \(15-\mathrm{kV}\) base in the zone of generator G2. Neglect \(\Delta-\mathrm{Y}\) transformer phase shifts.
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition
Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma