Faults at bus (n) in Problem 9.1 are of interest (the instructor selects (n=1), 2, or 3).

Question:

Faults at bus \(n\) in Problem 9.1 are of interest (the instructor selects \(n=1\), 2, or 3). Determine the Thévenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 per unit. Prefault load currents and \(\Delta-Y\) transformer phase shifts are neglected. 

Problem 9.1

The single-line diagram of a three-phase power system is shown in Figure 9.17. Equipment ratings are given as follows:

Synchronous generators:

image text in transcribed

Transformers:

image text in transcribed

Transmission lines:

image text in transcribed

The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a \(1000-\mathrm{MVA}, 765-\mathrm{kV}\) base in the zone of line 1-2. Neglect the \(\Delta-Y\) transformer phase shifts.

image text in transcribed

Step by Step Answer:

Related Book For  book-img-for-question

Power System Analysis And Design

ISBN: 9781305632134

6th Edition

Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma