Repeat Problems 9.1 and 9.14 including (Delta-Y) transformer phase shifts. Assume American standard phase shift. Also calculate
Question:
Repeat Problems 9.1 and 9.14 including \(\Delta-Y\) transformer phase shifts. Assume American standard phase shift. Also calculate the sequence components and phase components of the contribution to the fault current from generator \(n\) ( \(n=1,2\), or 3 as specified by the instructor in Problem 9.2).
Problem 9.1
The single-line diagram of a three-phase power system is shown in Figure 9.17. Equipment ratings are given as follows:
Synchronous generators:
Transformers:
Transmission lines:
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a \(1000-\mathrm{MVA}, 765-\mathrm{kV}\) base in the zone of line 1-2. Neglect the \(\Delta-Y\) transformer phase shifts.
Problem 9.14
Determine the subtransient fault current in per-unit and in kA, as well as the per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground fault at the fault bus selected in Problem 9.2.
Problem 9.2
Faults at bus \(n\) in Problem 9.1 are of interest (the instructor selects \(n=1\), 2, or 3). Determine the Thévenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 per unit. Prefault load currents and \(\Delta-Y\) transformer phase shifts are neglected.
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition
Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma