Figure 2.26 shows three loads connected in parallel across a (1000-mathrm{V}) (RMS), 60-Hz single-phase source. Load 1:
Question:
Figure 2.26 shows three loads connected in parallel across a \(1000-\mathrm{V}\) (RMS), 60-Hz single-phase source.
Load 1: Inductive load, \(125 \mathrm{kVA}, 0.28 \mathrm{PF}\) lagging.
Load 2: Capacitive load, \(10 \mathrm{~kW}, 40 \mathrm{kvar}\).
Load 3: Resistive load, \(15 \mathrm{~kW}\).
(a) Determine the total \(\mathrm{kW}\), kvar, kva, and supply power factor.
(b) In order to improve the power factor to 0.8 lagging, a capacitor of negligible resistance is connected in parallel with the above loads.
Find the kvar rating of that capacitor and the capacitance in \(\mu F\).
Comment on the magnitude of the supply current after adding the capacitor.