For Problem 3.18, the motor operates at full load, at 0.8 power factor leading, and at a
Question:
For Problem 3.18, the motor operates at full load, at 0.8 power factor leading, and at a terminal voltage of \(10.45 \mathrm{kV}\). Determine
(a) the voltage at bus 1 , which is the generator bus, and
(b) the generator and motor internal EMFs.
Problem 3.18
Using the transformer ratings as base quantities, work Problem 3.13 in per-unit.
Problem 3.13
A single-phase 50-kVA, 2400/240-volt, \(60-\mathrm{Hz}\) distribution transformer has a 1 -ohm equivalent leakage reactance and a 5000 -ohm magnetizing reactance referred to the high-voltage side. If rated voltage is applied to the high-voltage winding, calculate the open-circuit secondary voltage. Neglect \(I^{2} \mathrm{R}\) and \(\mathrm{G}_{c}^{2} \mathrm{~V}\) losses. Assume equal series leakage reactances for the primary and the referred secondary.
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition
Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma