A 5-MVA, 60-Hz, 6.6-kV, four-pole, 95% efficient round rotor synchronous generator has the synchronous reactance of 7.0

Question:

A 5-MVA, 60-Hz, 6.6-kV, four-pole, 95% efficient round rotor synchronous generator has the synchronous reactance of 7.0 Ω/phase and negligible armature resistance.

When operating at unity power factor, determine 

(1) The maximum power it can deliverer under steady state (no step load changes), 

(2) The power angle (the rotor lead angle), and

(3) Back torque on the rotor in Newton meters and in pound feet.