A three-phase 13.8-kV distribution center has a source (Thevenin) impedance of 0.5 + j2.5 /phase. Determine the
Question:
A three-phase 13.8-kV distribution center has a source (Thevenin) impedance of 0.5 + j2.5 Ω/phase. Determine the symmetrical rms and the worst-case asymmetrical first peak value of the fault current in a balanced three-phase fault at the distribution center bus.